Case study 01
Commercial LV Cabling Design
Evidence verified - sanitised write-up
Standards-traceable 400 V cabling design for a three-tenancy commercial complex: maximum demand, cable selection, earthing, and fault verification to AS/NZS 3000 and AS/NZS 3008.1.1.

Problem
What needed solving
Design the complete LV cabling system for a three-tenancy commercial complex supplied at 400 V from a 500 kVA transformer, and prove every cable and protective device against AS/NZS 3000:2018 and AS/NZS 3008.1.1:2025.
Approach
How the work is framed
Calculated per-phase maximum demand by the AS/NZS 3000 Clause 2.2.2(a) method, then ran one auditable nine-step selection chain per cable covering current capacity, de-rating, voltage drop, fault level, and earth-fault-loop impedance, with every assumption logged for verification against the controlling standard.
Result
Current public outcome
123.6 A design current met by 25 mm² X-90 copper consumer mains at 0.74 % voltage drop; 8.0 kA prospective fault current at the main switchboard confirmed 10 kA-rated Type C protection; every final subcircuit passed the AS/NZS 3000 Table 8.1 earth-fault-loop limits.
Evidence status
What still needs proof
Verified. Sanitised public write-up complete; full tabulated working held privately because standards tables are Standards Australia copyright.
Design detail
The full selection chain
Every cable in this design was selected with the same auditable nine-step chain: design current, protective device, installation method, correction factors, cable selection, voltage drop, fault withstand, earth-fault-loop check, final selection. The worked results below are my calculations; standards table data is cited by table number, not reproduced, because those tables are Standards Australia copyright.
Design basis
Three-tenancy commercial complex (a small supermarket, a hairdresser and a butcher, plus communal services), supplied at 400 V three-phase (230 V line-to-neutral) from a 500 kVA transformer with a stated prospective fault current of 15 kA at the transformer. Cable selection to AS/NZS 3008.1.1:2025; installation, earthing, protection and maximum demand to AS/NZS 3000:2018 (+ Amdt 1–3, Ruling 1:2024).
Maximum demand and phase balance
Maximum demand was determined by calculation per AS/NZS 3000:2018 Clause 2.2.2(a), using the Table C2 non-domestic diversity method. Every load was classified once, allocated to a phase, and group-diversity rules applied per phase; three-phase loads add their per-phase current to all three phases. The heaviest phase sets the design current: 123.6 A on phase A, with 7.5 % phase imbalance. Per board: communal 39.9 A, supermarket 39.1 A, hairdresser 24.5 A, butcher 41.8 A. The butcher is simultaneously the heaviest-loaded and longest (15 m) submain.
Consumer mains: worked chain
X-90 single-core copper, separate conduits laid in trefoil, buried 600 mm, soil 20 °C, 15 m route. AS/NZS 3008.1.1:2025 Table 3.8 routes this arrangement to Table 3.13, Column 19 (separately enclosed).
Step 1 Design current Ib = 123.6 A (heaviest phase)
Step 2 Protective device In = 125 A Type C (Ib <= In)
Step 3 Install method Table 3.8 -> Table 3.13, Col 19
Step 4 Correction k = 1.04 (soil, T3.45) x 0.99 (depth, T3.46)
= 1.03
Required tabulated CCC >= 125 / 1.03 = 121.4 A
Step 5 16 mm2 -> 101 A (fail); 25 mm2 -> 132 A (pass)
Iz = 132 x 1.03 = 136 A -> Ib 123.6 <= In 125 <= Iz 136 OK
Step 6 Voltage drop (limit 1 % = 4.0 V), Rc = 0.927 ohm/km
dV = sqrt3 x 123.6 x 15 x 0.927 / 1000 = 2.98 V = 0.74 % OK
Step 7 PFC at MSB = 8.0 kA; breaking capacity 10 kA OK
SELECT 25 mm2 X-90 Cu active and neutral; 6 mm2 Cu earthA single-conduit arrangement (Column 17) would instead require 35 mm²; that is not the arrangement specified. The result is current-carrying-capacity driven, not voltage-drop driven.
Submains: worst case worked
V-75 single-insulated copper, one conduit, buried 1 m, soil 20 °C. Table 3.8 routes this to Table 3.12, Column 17. Combined correction k = 1.05 × 0.95 = 1.00. The butcher submain governs.
Step 1 Ib = 41.8 A Step 2 In = 50 A Type C
Step 4 k = 1.00 -> required CCC >= 50 A
Step 5 6 mm2 -> 45 A (fail); 10 mm2 -> 59 A (pass); Iz = 59 A
Ib 41.8 <= In 50 <= Iz 59 OK
Step 6 dV = sqrt3 x 41.8 x 15 x 2.23 / 1000 = 2.42 V = 0.61 % OK
SELECT 10 mm2 V-75 Cu; 4 mm2 Cu earth
(16 mm2 recommended for practical margin)Final subcircuits: the thermal-insulation catch
The specification states thermal insulation in all ceiling spaces, and the final subcircuits clip across the ceiling joists, so the cables are not in free air. A cable clipped to a structural member within bulk insulation is a partially-surrounded thermal-insulation installation under AS/NZS 3008.1.1 Clause 3.4.3. Ratings were therefore read from the partially-surrounded column with the 45 °C ambient correction (Table 3.44, factor 0.93). This condition raised most power circuits from 2.5 mm² to 4 mm², the single most consequential installation-condition decision in the design.
| Load type | Run (m) | Ib (A) | In (A) | Cable | Iz (A) | ΔV | Earth |
|---|---|---|---|---|---|---|---|
| Lighting | 26 | 5.0 | 10 | 1.5 mm² | 11.2 | 1.87 % | 1.5 mm² |
| Power (10 A GPO) | 24 | 10 | 20 | 4 mm² | 21.4 | 1.17 % | 2.5 mm² |
| Power >10 A (15 A socket) | 15 | 15 | 20 | 4 mm² | 21.4 | 1.10 % | 2.5 mm² |
| Hot water service | 18 | 15.7 | 20 | 4 mm² | 21.4 | 1.37 % | 2.5 mm² |
| Cooking appliances | 15 | 11.3 | 16 | 4 mm² | 21.4 | 0.83 % | 2.5 mm² |
| Air-conditioning (3-ph) | 10 | 4.6/ph | 10 | 2.5 mm² | 15.8 | 0.18 % | 2.5 mm² |
| 3-phase 15 A outlet | 10 | 15/ph | 20 | 4 mm² | 21.4 | 0.36 % | 2.5 mm² |
All Iz ≥ In and every voltage drop is within budget; the worst-case total path (mains + butcher submain + lighting final) sums to 3.2 % against the 5 % limit.
Earthing and protection
Protective earthing conductors were sized from AS/NZS 3000:2018 Table 5.1 on the MEN system, main earth connected at the MSB neutral bar. Because the 25 mm² consumer-mains active was set by current-carrying capacity and not upsized for voltage drop, the 6 mm² main earth follows directly from Table 5.1. Type C circuit breakers were used throughout (suited to the low inrush of LED lighting, resistive heating and small motors), with 30 mA RCDs on all final subcircuits up to 32 A supplying socket-outlets and lighting. Nominal-current grading (125 A, then 40 to 50 A, then 10 to 20 A) gives current discrimination; full selectivity is to be confirmed against manufacturer time–current curves, a stated limitation of scope.
Fault level and earth-fault loop
Source impedance Zs = 400 / (sqrt3 x 15 000) = 0.0154 ohm/phase Consumer mains R = 0.884 x 15 / 1000 = 0.0133 ohm Z at MSB = 0.0154 + 0.0133 = 0.0287 ohm PFC at MSB = 230 / 0.0287 = 8 014 A = 8.0 kA
All device breaking capacities (10 kA) exceed the local prospective fault current. Earth-fault-loop impedance was checked for the longest circuit of each conductor size against AS/NZS 3000:2018 Table 8.1 for Type C breakers; the worst-case loop (4 mm² general-power final, 24 m, on the butcher submain) gives Zs ≈ 0.57 Ω against a limit of ≈ 1.15 Ω. The external loop impedance Ze = 0.0345 Ω is a declared assumption; the real figure comes from the network operator's connection-point fault data or an on-site loop-impedance measurement.
Declared assumptions and limits
Assumptions are logged explicitly rather than hidden: the socket-outlet diversity basis, the consumer-mains conduit arrangement (Column 19 basis confirmed against the controlled 2025 edition at transcription), the assumed Ze above, and discrimination pending manufacturer curves. The partially-surrounded ratings used were cross-checked against the 2017 edition and confirmed unchanged in the 2025 edition. Final values are to be verified against the controlling standards and network authority at installation. This write-up is sanitised from graded coursework: the design scenario is paraphrased, and no standards table content is reproduced.